A precision instrument suitable for calibrating and testing general purpose insulation testers and megohmmeters with test voltages up to 10 kV.
The 5069 is housed in a durable safety case and is powered by a rechargeable battery. This ensures full isolation from the mains and prevents stray leakage.
The insulation tester being calibrated can be tested for open circuit voltage and short circuit current. These are displayed on the digital meter mounted on the front panel. The insulation resistance is provided by a precision 4 dial decade resistance bank which can be set to a maximum of 99.99 GΩ with additional resistance values of 100 kΩ, 200 kΩ, 500 kΩ, 1 MΩ, 2 MΩ and 5 MΩ which can be switched in as required.
Rugged and portable, the 5069 is ideal for site calibration work. Also available is the 5068 Insulation Tester Calibrator, 2.5 kV version. For additional electrical testing capabilities the 5030 calibrator is a laboratory calibrator for multifunction installation testers.
Features
- 100 kΩ to 100 GΩ
- Basic accuracy 1 %
- Up to 10 kV operation
- Portable with battery operation
- Fully shrouded safety connectors
- Display of open circuit voltage
- Display of short circuit current
Specifications
Technical Specification
Resistance |
10 GΩ, 1 GΩ, 100 MΩ, 10 MΩ decade ranges. |
Fixed Values |
5 MΩ, 2 MΩ, 1 MΩ, 500 kΩ, 200 kΩ, 100 kΩ. |
Resistance Accuracy |
100 kΩ to 5 MΩ = 1%. 10 MΩ to 10 GΩ = 1%. 10 GΩ to 100 GΩ = 5%. |
Maximum Voltages |
100 kΩ, 200 kΩ, 500 kΩ: 500 V / 1 MΩ, 2 MΩ, 5 MΩ: 2 kV / 10 MΩ: 2 kV 20 MΩ: 4 kV / 30 MΩ to 10 GΩ: 6 kV / 10 GΩ to 100 GΩ: 10 kV NOTE: The maximum voltage applied must be limited to the rating of the lowest decade being used.
|
Resistance Temperature Coefficient |
Less than 250 ppm per °C |
Open Circuit Voltage Measure |
0 to 2 kV range, accuracy 1 % FS. 0 to 10 kV range, accuracy 2 % FS. |
Voltage Display |
1.999 kV full scale, and 10 kV full scale. |
Short Circuit Current Measure |
0 to 2 mA range and 0 to 20 mA range = 1 % FS accuracy. |
Current Display |
1.999 mA full scale, and 19.99 mA full scale. |
General Specification
Power |
Internal battery, 6 V re-chargeable NiCad, > 150 hours between charges. |
Dimensions |
W 406 x H 175 x D 330 mm |
Weight |
4.4 kg |
Supplied With |
Safety connection leads with bare end to allow custom probes (10 kV rated), 4 mm 5 kV test lead set, pouch to carry test leads, and mains charger. |
Optional Extras |
Calibration certificates: Traceable (factory) and accredited (ISO 17025). |
Country of Origin |
UK |
Shipping Details |
Packed Dimensions: L 77 x W 52 x H 30 cm / Packed Weight: 8 kg |
HS Code |
9030 3370 |